Figure 4-2 Grounding and high-frequency equipotential bonding measures in the control cabinet and
in the plant/system
Further information
Additional information about EMC-compliant installation is available in the Internet:
EMC installation guideline (
http://support.automation.siemens.com/WW/view/en/60612658)
4.1.2 Cables
Cables with a high level of interference and cables with a low level of interference are
connected to the inverter:
Cables with a high level of interference:
Cable between the line filter and inverter
Motor cable
Cable at the inverter DC link connection
Cable between the inverter and braking resistor
Cables with a low level of interference:
Cable between the line and line filter
Signal and data cables
Installing
4.1 EMC-compliant setup of the machine or plant
Converter with the CU230P-2 Control Units
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE 59