4.4.1 TN line system
A TN line system transfers the PE protective
conductor to the installed plant or system us‐
ing a cable.
Generally, in a TN line system the neutral
point is grounded. There are versions of a TN
system with a grounded line conductor, e.g.
with grounded L1.
A TN line system can transfer the neutral con‐
ductor N and the PE protective conductor ei‐
ther separately or combined.
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH6HSDUDWHWUDQVIHURI1DQG3(
JURXQGHGQHXWUDOSRLQW
/
/
/
1
3(
Inverter operated on a TN line system
Inverter with integrated or external line filter:
Operation on TN line systems with grounded neutral point permissible.
Operation on TN line systems with grounded line conductor not permissible.
Inverter without line filter:
Operation on all TN line systems ≤ 600 V permissible
Operation on TN line systems > 600 V and grounded neutral point permissible.
Operation on TN line systems > 600 V and grounded line conductor not permissible.
Installing
4.4 Connecting the line supply and motor
Converter with the CU230P-2 Control Units
84 Operating Instructions, 09/2017, FW V4.7 SP9, A5E34257946B AE