Commissioning
8.6 Procedure for configuring PROFIsafe communication
Safety Integrated
Function Manual, 05/2010, A5E03264275A
219
7. Set the PROFIBUS interface under the "Parameter" tab, set the address, and with the
"Properties..." button, set the network settings, the transmission rate (e.g. 12 Mbit/s), the
profile (DP) and then acknowledge with "OK". This sets up the master.
Figure 8-19 Setting the PROFIBUS profile
Creating a safety slave (drive)
1. The drive can either be selected in the catalog window under PROFIBUS-DP/SINAMICS
/SINAMICS S120/SINAMICS S120 CU320 or by installing a GSD file. Using the left
mouse button, drag the "SINAMICS S120 CU320-2" drive to the PROFIBUS line in the
upper lefthand window (the cursor has a + character) and release the mouse button. In
the following properties window, set the PROFIBUS address of the drive and exit the
following window with "OK".