EasyManua.ls Logo

Siemens SINAMICS G130 - Page 228

Siemens SINAMICS G130
312 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning
8.7 PROFIsafe via PROFINET
Safety Integrated
228 Function Manual, 05/2010, A5E03264275A
1. Under the drive module, select the "PROFIsafe" line and use the right-hand mouse key to
call up the properties of the PROFIsafe slot.
2. Define the address area of the PROFIsafe telegram under the "Addresses" tab. The start
address for inputs and output is identical. To confirm your entries, choose "OK".
Figure 8-28 Setting PROFINET addresses
3. Using the "PROFIsafe" tab, define the parameters important for Safety communication
("F parameters"). If the "PROFIsafe…" tab is inactive, then you can activate this button
for control using the "Activate..." button.
Figure 8-29 Setting F parameters

Table of Contents

Other manuals for Siemens SINAMICS G130

Related product manuals