Electrical installation
4.10 Signal connections
Inverter chassis units
114 Operating Instructions, 07/2016, A5E00331449A
Table 4- 46 Specification of measuring systems that can be connected
Parameters
Designation
Threshold
4)
Min.
Max.
Unit
High signal level
(TTL bipolar at X520 or X521/X531)
1)
U
Hdiff
2 5 V
Low signal level
(TTL bipolar to X520 or X521/X531)
1)
U
Ldiff
-5 -2 V
High signal level
(HTL unipolar)
U
H
4)
High
17
V
CC
V
Low
10
V
CC
V
Low signal level
(HTL unipolar)
U
L
4)
High
0
7
V
Low
0
2
V
High signal level
(HTL bipolar)
2)
U
Hdiff
3 V
CC
V
Low signal level
(HTL bipolar)
2)
U
Ldiff
-V
CC
-3 V
Signal frequency
f
S
-
300
kHz
Edge spacing
t
min
100
-
ns
Zero pulse inactive time
(before and after A=B=high)
t
Lo
640 (t
ALo-BHi
- t
Hi
)/2
3)
ns
Zero pulse active time
(while A=B=high and beyond)
t
Hi
640 t
ALo-BHi
- 2 x t
Lo
3)
ns
1)
Other signal levels according to the RS 422 standard.
2)
The absolute level of the individual signals varies between 0 V and V
CC
of the measuring
system.
3)
t
ALo-BHi
is not a specified value, but is the time between the falling edge of track A and the
next but one rising edge of track B.
4)
The threshold can be set via p0405.04 (switching threshold); the setting on delivery is
"Low."
Figure 4-26 Signal characteristic of the A and B track between two edges: time between two edges
with pulse encoders