Electrical installation
4.10 Signal connections
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
117
4.10.5.2
Connection
X500: DRIVE-CLiQ interface
Table 4- 47 DRIVE-CLiQ interface X500
Pin
Signal name
Technical data
1
TXP
Transmit data +
2
TXN
Transmit data -
3
RXP
Receive data +
4 Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronics ground
Blanking plate for DRIVE-CLiQ interfaces (50 pcs.) Article number: 6SL3066-4CA00-0AA0
X524: Electronic power supply
Table 4- 48 Terminal block X524
Terminal
Function
Technical data
+
Electronic power supply
Voltage: 24 VDC (20.4 to 28.8 V)
Current consumption: max. 0.55 A
Max. current via jumper in connector: 20 A (15 A
according to UL/CSA)
+
Electronic power supply
M
Electronics ground
M Electronics ground
Max. connection cross-section: 2.5 m
The maximum cable length that can be connected is 10 m.
Note
Looping through the supply voltage
The two "+" and "M" terminals are jumpered in the connector and not in the unit.
This ensures that the supply voltage is looped through.
The power can be supplied via terminals X41:1/2 of the Power Module.