Commissioning
5.3 Procedure for commissioning via STARTER
Inverter chassis units
142 Operating Instructions, 07/2016, A5E00331449A
Select the corresponding settings for the closed-loop control structure:
Function modules:
Technology controller
Extended messages/monitoring
Control:
n/M control + U/f control, I/f control
U/f control
Control mode:
Depending on the selected control, you can select from one of the following open-
loop/closed-loop control modes:
0: U/f control with linear characteristic
1: U/f control with linear characteristic and FCC
2: U/f control with parabolic characteristic
3: U/f control with parameterizable characteristic
4: U/f control with linear characteristic and ECO
5: U/f control for drive requiring a precise frequency (e.g. textiles)
6: U/f control for drive requiring a precise frequency and FCC
7: U/f control with parabolic characteristic and ECO
15: Operation with braking resistor
18: I/f control with fixed current
19: U/f control with independent voltage setpoint
20: Speed control (without encoder)
21: Speed control (with encoder)
22: Torque control (without encoder)
23: Torque control (with encoder)