Commissioning
5.3 Procedure for commissioning via STARTER
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
165
STARTER via Ethernet (example)
Figure 5-34 STARTER via Ethernet (example)
Procedure for establishing online operation via Ethernet
1. Install the Ethernet interface in the PG/PC according to the manufacturer's specifications.
2. Set the IP address of the Ethernet interface in Windows.
Assign the PG/PC a free IP address (e.g. 169.254.11.1 ).
The factory setting for the internal Ethernet interface -X127 of the Control Unit is
169.254.11.22.
3. Set the access point of the STARTER commissioning tool.
4. Use the STARTER commissioning tool to specify a name for the Control Unit interface.
The Ethernet interface must be initialized so that the STARTER can establish
communication. Selecting online mode in STARTER.
Setting the IP address in Windows 7
Note
The following procedure refers to the Windows 7 operating system. Operation can
differ
slightly for other operating systems (e.g. Windows XP).
1. In the PG/PC call the control panel using the "Start > Control Panel" menu item.
2. In the control panel of your PG/PC, under "Network and Internet", select the "Network and
Sharing Center" function.
3. For your network card that is displayed, click the connection link.
4. Click in the status dialog of the connection on "Properties" and acknowledge the
subsequent confirmation prompt with "Yes".
5. In the properties dialog of the connection, select the "Internet protocol 4 (TCP/IPv4)"
element and then click "Properties".
6. In the properties dialog, activate the "Use the following IP address" option.