Commissioning
5.6 Status after commissioning
Inverter chassis units
182 Operating Instructions, 07/2016, A5E00331449A
5.6
Status after commissioning
LOCAL mode (control via operator panel)
You switch to LOCAL mode by pressing the "LOCAL/REMOTE" key.
Control (ON/OFF) is carried out via the "ON" and "OFF" keys.
You can specify the setpoint using the "increase" and "decrease" keys or by entering the
appropriate numbers using the numeric keypad.
Analog outputs (for version with TM31)
The actual speed (r0063) is output as a voltage output in the range 0 to 10 V at analog
output 0 (X522:1, 2).
10 V is equal to the maximum speed in p1082.
The actual current value (r0068) is output as a voltage output in the range 0 to 10 V at
analog output 1 (X522:4, 5).
10 V corresponds to the current limit (p0640), which is set to 1.5 x the rated motor current
(p0305).
Digital outputs (for version with TM31)
The "enable pulses" signal is output at digital output 0 (X542:2 and 3).
The “no fault active” signal is output at digital output 1 (X542:5 and 6) (protection against
wire breakage).
The "ready to start" signal is output at digital output 8 (X541:2).