Operation
6.5 Setpoint sources
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
215
Signal flow diagram
Figure 6-18 Signal flow diagram: Motorized potentiometer
Function diagram
FD 3020
Motorized potentiometer
Parameter
p1030
Motorized potentiometer, configuration
p1037
Motorized potentiometer, maximum speed
p1038
Motorized potentiometer, minimum speed
p1047
Motorized potentiometer, ramp
-up time
p1048
Motorized potentiometer, ramp
-down time
r1050
Motorized potentiometer, setpoint after the ramp
-function generator
6.5.3
Fixed speed setpoints
Description
A total of 15 variable fixed speed setpoints are available.
The default setting specified for the setpoint sources during commissioning via STARTER or
the operating panel makes three fixed speed setpoints available. They can be selected via
terminals or fieldbus.