EasyManua.ls Logo

Siemens SINAMICS G130 - Structure of the Telegrams

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6.6 Communication according to PROFIdrive
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
223
Note
Easy method for creating extended telegram interconnections
If p0922 = 999, a telegram can be selected in p2
079. A telegram interconnection is
automatically made and blocked. However, the telegram can also be extended.
This is an easy method of creating extended telegram interconnections on the basis of
existing telegrams.
6.6.3.2
Structure of the telegrams
Table 6- 9 Structure of the telegrams
Telegr.
PZD 1
PZD 2
PZD 3
PZD 4
PZD 5
PZD 6
PZD 7
PZD 8
PZD 9
PZD 10
1
STW1
NSOLL_A
ZSW1
NIST_A
2
STW1
NSOLL_B
STW2
ZSW1 NIST_B ZSW2
3
STW1
NSOLL_B
STW2
G1_STW
ZSW1 NIST_B ZSW2 G1_ZSW G1_XIST1 G1_XACT2
4
STW1
NSOLL_B
STW2
G1_STW
G2_STW
ZSW1
NIST_B
ZSW2
G1_ZSW
Further assignment, see FP2420
20
STW1
NSOLL_A
ZSW1 NIST_A_
GLATT
IAIST_
GLATT
MIST_
GLATT
PIST_
GLATT
MELD_
NAMUR
220 STW1_
BM
NSOLL_B STW2_BM M_ADD M_LIM free free free free
ZSW1_
BM
NIST_A IAIST MIST WARN_
CODE
FAULT_
CODE
ZSW2_
BM
free free free
352
STW1
NSOLL_A
PCS7_3
PCS7_4
PCS7_5
PCS7_6
ZSW1 NIST_A_
GLATT
IAIST_
GLATT
MIST_
GLATT
WARN_
CODE
FAULT_
CODE
999
STW1
free
free
free
free
free
free
free
free
free
ZSW1
free
free
free
free
free
free
free
free
free

Table of Contents

Other manuals for Siemens SINAMICS G130