Operation
6.6 Communication according to PROFIdrive
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
235
Information about the parameter response:
Request reference mirrored:
This response belongs to the request with request reference 25.
Response identifier:
01 hex → Read request positive, values available starting from 1st value
Request reference mirrored:
The values correspond to the values from the request.
Format:
06 hex → Parameter values are in the unsigned16 format.
Number of values:
08 hex → 8 parameter values are available.
1st value ... 8th value:
In the fault buffer of drive 2, a fault is only entered in the 1st value.
6.6.4.4
Example 2: Writing parameters (multi-parameter request)
Preconditions
The PROFIdrive controller has been commissioned and is fully operational.
PROFIdrive communication between the controller and the device is operational.
The controller can read and write data sets in conformance with PROFINET/PROFIBUS.
Special requirements for this example:
Control mode: Vector control (with extended setpoint channel)
Task description
Jog 1 and 2 are to be set up for drive 2 (also drive object number 2) via the input terminals of
the Control Unit. A parameter request is to be used to write the corresponding parameters as
follows:
BI: p1055 = r0722.4
Jog bit
0
BI: p1056 = r0722.5
Jog bit
1
p1058 = 300 rpm
Jog 1 speed setpoint
p1059 = 600 rpm
Jog 2 speed setpoint
The request is to be handled using a request and response data block.