Siemens SINAMICS G130 - Transition into the Energy-Saving Mode from the Profidrive Operating State (S4)

Siemens SINAMICS G130
610 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation
6.8 Communication via PROFINET IO
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
267
General converter behavior when in the PROFIenergy energy-saving mode
When the PROFIenergy energy-saving mode is active, the converter issues alarm
A08800.
When the PROFIenergy energy-saving mode is active, the converter does not send any
diagnostic alarms.
If the bus connection to the control system is interrupted while the converter is in the
energy-saving mode, the converter exits the energy-saving mode and resumes normal
operation ("ready_to_operate").
The converter changes into normal operation if the control system goes into the stop
condition while the converter is in the energy-saving mode.
6.8.4.7
Transition into the energy-saving mode from the PROFIdrive operating state (S4)
If you set p5611.2 = 1, you enable transition to the energy-saving mode from the PROFIdrive
operating state (S4)
To do so, you must set one of the following settings:
p5611.1 = 1: With the transition to the energy-saving mode, the converter issues an
OFF1 command and enters the start-inhibit state (S1).
p5611.1 = 0: You can use p5614 to interconnect a signal source that switches the
converter off and places it in the start-inhibit state (S1).
If the control sends the command "End_Pause" or "Start_Pause" with a pause time of 0, the
converter continues to run automatically if the enables are still set.
6.8.4.8
Inhibit PROFIenergy and idle time
Inhibit PROFIenergy
If you set p5611.0 = 1, you inhibit the response of the converter to PROFIenergy control
commands. In this case, the converter ignores the PROFIenergy control commands.
Pause time
Minimum pause time: p5602
When the pause time, which is sent using command "Start_Pause", is equal to or
greater than the value in p5602[1], then the converter goes into the energy-saving
mode.
If the pause time is less than p5602[1], the converter ignores the command.
Maximum duration: p5606