6.9 Communication via SINAMICS Link
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
273
Bus cycle and number of nodes
The bus cycle of SINAMICS Link can be operated, synchronized with the current control
cycle, or not synchronized.
Synchronized operation is set with p8812[0] = 1.
Up to 16 stations with 500 µs bus cycle can communicate with one another via
SINAMICS Link. To do this, the maximum number of nodes must be set with p8811 = 16.
Up to 64 stations with 1000 µs or 2000 µs bus cycle can communicate with one another
via SINAMICS Link. To do this, the maximum number of nodes must be set with
p8811 = 64.
In non-synchronized operation (p8812[0] = 0), the PZD sampling time (p2048/p8848) is
effective instead of the bus cycle (p8812[1]).
After changing over parameter p8811 and p8812, a POWER ON must be carried out to
accept the settings.
6.9.2
Topology
Only a line topology with the following structure is permitted for SINAMICS Link.
Figure 6-34 Maximum topology