Operation
6.10 Communication via EtherNet/IP
Inverter chassis units
286 Operating Instructions, 07/2016, A5E00331449A
Configuring communication
Make the communication settings
Make the following settings for the CBE20 in order to communicate with a higher-level
control via EtherNet/IP:
1. With p8835 = 4, set the firmware version "Ethernet/IP".
2. Set the IP address using p8941.
You can find the currently valid address in r8951.
3. Set the subnet mask using p8943.
You can find the currently valid subnet mask in r8953.
4. Set the standard gateway using p8942.
You can find the currently valid standard gateway in r8952.
5. Set the station name using p8940.
You can find the currently valid station name in r8950.
6. Set "Save and activate configuration" as interface configuration with p8945 = 2.
7. Save the data using command "Copy RAM to ROM".
8. Perform a POWER ON.
Your settings become active after switching on.
Supported objects
Overview
6 hex 6 Connection Management Object x -
Siemens Motor Data Object
1)
1)
Adapter Diagnostic Object
Explicit Messages Diagnostic Object
Explicit Message Diagnostic List Object