Operation
6.10 Communication via EtherNet/IP
Inverter chassis units
290 Operating Instructions, 07/2016, A5E00331449A
Table 6- 37 Class Attribute
2 get UINT16 Max Instance
Table 6- 38 Instance Attribute
2 get, set Commisioning state p0010: commissioning parameter filter
3 … 18 get STW1 STW1 bit-by-bit access:
Attr. 3 = STW1.0
20 … 35 get ZSW1 ZSW1 bit-by-bit access:
Attr. 20 = ZSW1.0
Main actual value (actual frequency)
p1120[0]: ramp-function generator ramp-up time
38 get, set Ramp Down Time p1121[0]: ramp-function generator ramp-down
42 get, set OFF3 Ramp Down
p1135[0]: OFF3 ramp-down time
p2200[0]: Technology controller enable
44 get, set PID Filter Time Con-
p2265: Technology controller actual value filter
45 get, set PID D Gain p2274: technology controller differentiation time
p2280: technology controller proportional gain
47 get, set PID I Gain p2285: technology controller integral time
p2291: technology controller maximum limiting
p2292: technology controller minimum limiting
r0026[0]: DC link voltage
r0027: current actual value
r0031: actual torque value
r0032: active power actual value
r0035[0]: motor temperature
58 get Power Unit Tempera-
r0037[0]: power unit temperature