Operation
6.10 Communication via EtherNet/IP
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
293
Table 6- 42 Instance Attribute
No.
Service
Type
Name
Value/explanation
1 get UNIT32 Status Fixed value: 1 hex
1: Configuration acknowledged, by DHCP or
saved values
2 get UNIT32 Configuration
Capability
Fixed value: 94 hex
4 hex: DHCP supported,
10 hex: Configuration can be adjusted,
80 hex: ACD-capable
3 get, set UNIT32 Configuration
Control
1 hex: Saved values
3 hex: DHCP
4 get, set UNIT16 Path Size (in
WORDs)
Fixed value: 2 hex
UNIT8 Path 20 hex,
F6 hex,
24 hex,
05 hex, where 5 hex is the number of instances of
F6 hex (four physical ports plus one internal port).
5 get, set
STRING
Interface Configu-
ration
r61000: name of station
UNIT32
r61001: IP address
6 get, set
UNIT16
Host Name
Host Name Length
STRING
-
10 get, set UNIT8 Select ACD local OM flash:
0: Disabled,
1: Enabled
11 get, set UNIT8 Last Conflict De-
tected
local OM flash ACD Activity
UNIT8
local OM flash Remote MAC
UNIT8
local OM flash ARP PDU
Link Object, Instance Number: F6 hex
Supported services
Class
Get Attribute all
Get Attribute single
Instance
Get Attribute all
Get Attribute single
Set Attribute single
Table 6- 43 Class Attribute
No.
Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances