Operation
6.11 Communication via MODBUS TCP
Inverter chassis units
304 Operating Instructions, 07/2016, A5E00331449A
Table 6- 49 Assignment of the Modbus register for general parameter access using DS47
ON/OFF text
or Value range
40602 DS47 header R/W - - - -
Note
Limited value range
Modbus TCP registers have a maximum 16 bit width. The values of display parameters (r
parameters) cannot always be represented with 16 bits. In these particular cases, the
maximum value that can be represented is disp
layed.
Unsigned: 65535
Signed min: -32768
Signed max: 32767
Write and read access using function codes
Function codes used
For data exchange between the master and slave, predefined function codes are used for
communication via Modbus.
The Control Unit uses the following Modbus function codes:
● FC 03: Holding register to read data from the inverter
● FC 06: Write single register to write to individual register
● FC 16: Write to multiple registers to write to several registers
Structure of a Modbus TCP message
Table 6- 50 Individual components, including Modbus Application Header (MBAP) and function code
Application Data Unit (ADU)
Modbus Application Header