Operation
6.11 Communication via MODBUS TCP
Inverter chassis units
310 Operating Instructions, 07/2016, A5E00331449A
Table 6- 63 Response for successful write operation
Function code (read)
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
0002 h
2F04 h
8002 h
9,10
11,12
13,14
40601: DS47 Control = 2 (request was executed)
40602: Function code 2F h (47), response length 4 bytes
40603: Request reference mirrored = 80 h,
response identifier = 2 (change parameter)
40604: DO-ID = 1, number of parameters = 1
Table 6- 64 Response for unsuccessful write operation - write request still not completed
MBAP header
03 h
7
Function code (read)
Number of following data bytes (20 h: 32 bytes ≙ 16 registers)
2F00 h
0004 h
11,12
13,14
40601: DS47 Control = 1 (request is processed)
40602: Function 2F h(47), response length 0 (fault)
40603: Error code: 0004 Response Not Ready (response has still not been
Communication procedure
Logical error
If the slave detects a logical error within a request, it responds to the master with an
"exception response". In the response, the slave sets the highest bit in the function code to
1. If the slave receives, for example, an unsupported function code from the master, the
slave responds with an "exception response" with code 01 (Illegal function code).
Table 6- 65 Overview of exception codes
01 Illegal function code An unknown (unsupported) function code was sent to the
An invalid address was requested.
An invalid data value was detected.
Slave has terminated during processing.