Setpoint channel and closed-loop control
7.4 Vector speed/torque control with/without encoder
Inverter chassis units
352 Operating Instructions, 07/2016, A5E00331449A
The ramp-up and ramp-down times should always be set to values larger than the startup
time.
Note
Setting the ramp-function generator
The ramp
-up and ramp-down times (p1120; p1121) of the ramp-function generator in the
setpoint channel should be set accordingly so that the motor speed can track the setpoint
during acceleration and braking. This will optimize the function of speed cont
roller pre-
Acceleration pre-control using a connector input (p1495) is activated by the parameter
settings p1400.2 = 1 and p1400.3 = 0. p1428 (dead time) and p1429 (time constant) can be
set for balancing purposes.
Precontrol balancing reference/acceleration model
p0311
r0333
p0341
p0342
Ratio between the total and motor moment of inertia
r0345
p1400.2
-control source
p1428
-control balancing dead time
p1429
-control balancing time constant
p1496
-control scaling
r1518
Reference model
Description
The reference model is activated with p1400.3 = 1.
The reference model is used to emulate the speed control loop with a P speed controller.
The loop emulation can be set in p1433 to p1435. It becomes effective if p1437 is connected
to the output of the model r1436.