Loading...
Functions, monitoring, and protective functions
9.3 Extended functions
Inverter chassis units
450 Operating Instructions, 07/2016, A5E00331449A
9.2.23.5
Overview of important parameters
r8911
IE IP Address of Station active
r8931
PN IP Address of Station active
p8986
Web server configuration
p8987[0...1]
Web server port assignment
9.3
Extended functions
9.3.1
Technology controller
Description
The "technology controller" function module allows simple control functions to be
implemented, e.g.:
Level control
Temperature control
Dancer roll position control
Pressure control
Flow control
Simple control without higher-level control
Tension control
The technology controller features:
Two scalable setpoints
Scalable output signal
Separate fixed values
Integrated motorized potentiometer
The output limits can be activated and deactivated via the ramp-function generator.
The D component can be switched to the system deviation or actual value channel.
The motorized potentiometer of the technology controller is only active when the drive
pulses are enabled.
The technology controller is designed as a PID controller, whereby the differentiator can be
switched to the control deviation channel or the actual value channel (factory setting). The P,
I, and D components can be set separately.