Functions, monitoring, and protective functions
9.4 Monitoring and protective functions
Inverter chassis units
480 Operating Instructions, 07/2016, A5E00331449A
Stall protection (only for vector control)
Description
If, for closed-loop speed control with encoder, the speed threshold set in p1744 for stall
detection is exceeded, then r1408.11 (speed adaptation, speed deviation) is set.
If the fault threshold value set in p1745 is exceeded when in the low speed range (less than
p1755 x (100% - p1756)), r1408.12 (motor stalled) is set.
If one of these two signals is set, then after the delay time in p2178, fault F07902 (motor
stalled) is returned.
Figure 9-28 Stall protection
- Interface to Motor Module (ASM, p0300 = 1)
Messages and monitoring - Torque messages, motor blocked/stalled
r1408
CO/BO: Control status word 3
p1744
model speed threshold stall detection
p1745
Motor model error threshold stall detection
p1755
Motor model changeover speed encoderless operation
p1756
Motor model changeover speed hysteresis encoderless operation
p2178