Functions, monitoring, and protective functions
9.4 Monitoring and protective functions
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
483
9.4.5.4
Temperature sensor connection directly at the Control Interface Module
Temperature measurement via KTY
The device is connected to terminals X41:3 (Temp-) and X41:4 (Temp+) on the Control
Interface Module in the forward direction of the diode.
Activate motor temperature measurement via Motor Module: p0600 = 11.
Set the KTY temperature sensor type: p0601 = 2.
Temperature measurement via PTC
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. The threshold for changing over to an alarm or fault is 1650 Ω.
Activate motor temperature measurement via Motor Module: p0600 = 11.
Set the PTC temperature sensor type: p0601 = 1.
Temperature measurement using the bimetal normally closed contact
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. The threshold for changing over to an alarm or fault is 100 Ω.
Activate motor temperature measurement via Motor Module: p0600 = 11.
Set the temperature sensor type bimetal normally closed contact: p0601 = 4.
Temperature measurement via PT100
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module. p0624 can be used to set the temperature offset for the PT100 measured
value.
Activate motor temperature measurement via Motor Module: p0600 = 11.
Set the PT100 temperature sensor type: p0601 = 5.
Temperature measurement via PT1000
The connection is made at the terminals X41:3 (Temp-) and X41:4 (Temp+) at the Control
Interface Module.
Activate motor temperature measurement via Motor Module: p0600 = 11:
Set the PT1000 temperature sensor type: p0601 = 6.