Diagnosis / faults and alarms
10.2 Diagnosis
Inverter chassis units
502 Operating Instructions, 07/2016, A5E00331449A
Control Interface Module – Interface module in the Power Module
Table 10- 4 Description of the LEDs "READY" and "DC LINK" on the Control Interface Module
Off Off The electronic power supply is missing or lies outside the permissible tolerance
Green ---
1)
The component is ready for operation and cyclic DRIVE-CLiQ communication is
Orange The component is ready for operation and cyclic DRIVE-CLiQ communication is
taking place.
The DC link voltage is present.
Red The component is ready for operation and cyclic DRIVE-CLiQ communication is
taking place.
The DC-link voltage lies outside the permitted tolerance range.
DRIVE-CLiQ communication is being established.
Red ---
1)
This component has at least one fault.
The LED is activated irrespective of whether the corresponding messages have been
reconfigured.
Flashing light
0.5 Hz:
---
1)
Firmware is being downloaded.
Flashing light 2
Hz:
---
1)
Firmware download is complete. Waiting for POWER ON.
Flashing light 2
Hz:
green/orange
or
---
1)
Detection of the components via LED is activated (p0124).
Note:
Both options depend on the LED status when module recognition is activated via
p0124 = 1.
1)
Irrespective of the status of the LED "DC LINK"
Table 10- 5 Meaning of the LED "POWER OK" on the Control Interface Module
POWER OK Green
DC link voltage < 100 V and voltage at -X9:1/2 less than 12 V.
The component is ready for operation.
Flashing
There is a fault. If the LED continues to flash after you have performed
a POWER ON, please contact your Siemens service center.
Danger to life when live parts of the DC link are touched
Irrespective of the state of the LED "DC LINK", hazardous DC link voltages can always be
present. This means that if live parts are touched, this can result in death or serious injury.
• Observe the warning information on the component.