Electrical installation
4.5 EMC-compliant design
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
51
Table 4- 2 Definition of categories C1 ... C4
Definition of categories C1 ... C4
Category C1
Rated voltage <1000 V; unrestricted use in the first environment.
Category C2 Rated voltage for stationary drive systems <1000 V; for use in the second
environment. For use in the first environment only when sold and installed
by skilled personnel.
Category C3
Rated voltage <1000 V; use in the second environment only.
Category C4 Rated voltage ≥1000 V or for rated currents ≥ 400 A in complex systems in
the second environment.
4.5
EMC-compliant design
The following section provides some basic information and guidelines that will help you
comply with the EMC and CE guidelines.
cabinet assembly
Connect painted or anodized metal components using toothed self-locking screws or
remove the insulating layer.
Use unpainted, de-oiled mounting plates.
Establish a central connection between ground and the protective conductor system
(ground).
Shield gaps
Bridge shield gaps (at terminals, circuit breakers, contactors, and so on) with minimum
impedance and the greatest possible surface area.
Using large cross-sections
Use underground and grounding cables with large cross-sections or, better still, with litz
wires or flexible cables.
Laying the motor supply cable separately
The distance between the motor cable and signal cable should be > 20 cm. Do not lay
signal cables and motor cables in parallel to each other.
Laying the equipotential bonding cable
It is recommended to lay the equipotential bonding cable parallel to the control lines with
a minimum cross-section of 16 mm
2
.