Appendix
A.2 Parameter macros
Inverter chassis units
Operating Instructions, 07/2016, A5E00331449A
591
Parameter macros
Parameter macro p0015 = G130 built-in unit
This macro is used to make default settings for operating the built-in unit.
Table A- 1 Parameter macro p0015 = G130 built-in unit
p0405[0] Square-wave encoder track A/B Vector 9h Bipolar, like A/B track Vector
1024 pulses per revolution
Encoder connection = terminal
p0600 Motor temperature sensor for moni-
Vector 0 No sensor Vector
Motor temperature sensor type
p0604 Motor overtemperature alarm
Vector 120 120 °C Vector
p0605 Motor overtemperature fault
Vector 155 155 °C Vector
Motor overtemperature timer
p0610 Response to motor overtempera-
Vector 12 Messages, no reduction of I_max,
Vector
Macro binector input (BI)
p1000[0] Macro connector inputs (CI) for
Vector 100001 PROFIdrive Vector
CO: Fixed speed setpoint 1
p1002 CO: Fixed speed setpoint 2 Vector 600 600 rpm Vector
CO: Fixed speed setpoint 3
p1083 CO: Speed limit in positive direction
Vector 6000 6000 rpm Vector
p1086 CO: Speed limit in negative direc-
Vector -6000 -6000 rpm Vector
p1115 Ramp-function generator selection Vector 1 Extended ramp-function genera-
Vector
p1120 Ramp-function generator ramp-up
Vector 20 20 s Vector
p1121 Ramp-function generator ramp-
Vector 30 30 s Vector
Flying restart operating mode
Flying restart not active