List of messages
Display messages
05/2020, 4BS0576F-004
19
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
2264 !!Suppressed fault!! Overcurrent V FtS>Overcurr. V ditto
2265 !!Suppressed fault!! Overcurrent W FtS>Overcurr. W ditto
2266 !!Suppressed fault!! Zero trace faulty FtS>Zero trace ditto
2275 !! Prewarning !! Standby fan Wrg>Stdst.fan Fan monitoring has tripped.
Re-engage the automatic circuit breakers –F8 and –F9; recheck the fan of
the device;
recheck input at PCB Signals –A13-X81:8 : 24V=good, 0V=warning
2292 !! Prewarning !! SNTP sync. Wrg>SNTP sync. Synchronization of the internal clock via SNTP not successful.
Check your network access, the parameterized IP-address and the acces-
sibility of the NTP server.
2500 !! Fault !! P-failure 13/T= as no. 3180 as no. 3180 P-failure 13: as no. 3180
2501 !! Fault !! P-failure 14/T= as no. 3180 as no. 3180 P-failure 14: as no. 3180
2502 !! Fault !! P-failure 15/T= as no. 3180 as no. 3180 P-failure 15: as no. 3180
2503 !! Fault !! P-failure 16/T= as no. 3180 as no. 3180 P-failure 16: as no. 3180
2541 !! Fault !! Overcurrent U Flt>Overcurr. U Overcurrent at inverter phase U; The inverter could not regulate the load
changes. Adjust the acc. Time slowlier. Damp the load. Contact our service
station.
2542 !! Fault !! Overcurrent V Flt>Overcurr. V Overcurrent at inverter phase V; The inverter could not regulate the load
changes. Adjust the acc. Time slowlier. Damp the load. Contact our service
station.
2543 !! Fault !! Overcurrent W Flt>Overcurr. W Overcurrent at inverter phase W; The inverter could not regulate the load
changes. Adjust the acc. Time slowlier. Damp the load. Contact our service
station.
2545 !! Fault !! Zero trace faulty Flt>Zero trace With field-oriented control (FOC) and synchronous motors only: the re-
quired zero line of speed sensor is not correctly connected or defective.
Recheck the connected sensor with its wiring. Following sensors could be
concerned: Sin-cos-output, wired to plug –X25. TTL-output, wired to plug
-X25. HTL-output, wired to plug –X101
2600 !! Fault !! P-failure 13/T= as no. 3180 as no. 3180 P-failure 13: as no. 3180
2601 !! Fault !! P-failure 14/T= as no. 3180 as no. 3180 P-failure 14: as no. 3180
2602 !! Fault !! P-failure 15/T= as no. 3180 as no. 3180 P-failure 15: as no. 3180
2603 !! Fault !! P-failure 16/T= as no. 3180 as no. 3180 P-failure 16: as no. 3180
2641 !! Fault !! Overcurrent U Flt>Overcurr. U as no. 2541, but not retained
2642 !! Fault !! Overcurrent V Flt>Overcurr. V as no. 2542, but not retained
2643 !! Fault !! Overcurrent W Flt>Overcurr. W as no. 2543, but not retained