List of messages
Display messages
26 05/2020, 4BS0576F-004
Text for event memory entry
3105 Fault SC phase U Flt>Short Ph.U - Short in inverter phase U; repair short in conductor inverter output/motor or
within the motor; if necessary, contact our service station.
3106 Fault SC phase V Flt>Short Ph.V - Short in inverter phase V; repair short in conductor inverter output/motor or
within the motor; if necessary, contact our service station.
3107 Fault SC phase W Flt>Short Ph.W -
Short in inverter phase W; repair short in conductor inverter output/motor or
within the motor; if necessary, contact our service station.
3108 Fault Fault tacho Flt>Fault Tacho high With field-oriented control (FOC) only: the required speed sensor is not
correctly connected or defective. Recheck the connected sensor with its
wiring.
Following sensors could be concerned: Sin-cos-output, wired to plug –
TTL-output, wired to plug –X25. HTL-output, wired to plug –X101
3113 Fault T-CPU too high Flt>T-CPU too hi mean Temperature on PCB Control electronics –A1 too high (cutoff at 75°C).
Cool down the operation environment; reduce the load; clean the air filter.
3114 Fault T-CPU too low Flt>T-CPU too low mean Temperature on PCB Control electronics –A1 too low (cutoff at -5°C). Heat
up operation environment.
3115 Fault T-cooler too high Flt>T-Cool. t.hi mean Temperature at dissipators too high (cut-off temp. depending on the de-
vice). Cool down the operation environment; reduce the load; clean the air
filter; recheck the fan of the device.
3116 Fault T-cooler too low Flt>T-Cool.t.low mean Temperature at dissipators too low (cut-off at -5° C).
Heat up the operation environment.
3117 Fault T-cooler 1 too high Flt>T-Cool.1 t.hi Temperature at dissipator 1 too high (cut-off temp. depending on the de-
vice). Cool down the operation environment; reduce the load; clean the air
filter; recheck the fan of the device.
3125 Fault Diff set/act Flt>Diff set/act low With field-oriented control (FOC) only: read-
out inverter output frequency is
not plausible regarding the speed that is fed-back by the speed sensor.
Recheck the parameterizing at "P-MACHINE POWER CONF/P-motor
data/Sensor" or "Pulses/360" or sensor signals. Recheck the connected
sensor HTL/TTL or sincos at plugs –X25 or -X101, possibly the tracks are
mixed up.
3126 Fault Set/act-sign Flt>Set/act-sign low With field-oriented control (FOC) only: the drive runs in opposite direction,
related to the read-out rotating field. Cause e.g. wrong connection of the
lines for the motor or the sensor : recheck the motor or sensor lines and
connect correctly; Recheck whether the parameterizing at "P-MACHINE
POWER CONF/P-motor data:Sensor" or at "Pulses/360" or the sensor
signals correspond with the actually installed sensor.
3127 Fault MainsPhaseRectifier1 Flt>MainsPh.Rec.1 high A mains phase at inverter rectifier 1 has failed: recheck the mains fuses;
measure the line voltage.