Text for event memory entry
3128 Fault MainsPhaseRectifier2 Flt>MainsPh.Rec.2 high A mains phase at inverter rectifier 2 has failed: recheck the mains fuses;
measure the line voltage.
3129 Fault Interruption BUS Flt>Interrpt. BUS - The fault occurs when:
- the external bus is not correctly connected or is disconnected
- at "P-INTERFACES/P-Fieldbus/Rct.BUS=fault" is parameterized and
- a bus-setp. value or act. value resp. op.-source has been parameterized.
If you have the bus, carry out the connection/ commissioning acc. to de-
scription 4BS0751, chapter Options/bus-PCBs. Recheck the bus-status on
the basis of the available control-LEDs on the bus-PCB.
If you have got no bus at all, recheck the parameter setting at
"P-INTERFACES/Op.-source=BUS" or "Reset-source=BUS", or in the
menus "P-speed default, P-process control, P-T-control, P-current control"
a parameter is set to BUS. relocate these parameters to another source.
3130 Fault BUS Hardware Flt>BUS Hardware - The fault occurs when:
- the inverter-internal connection to the bus does not work correctly
- at "P-INTERFACES/P-Fieldbus/Rct.BUS=fault" is parameterized and
- a BUS-setp. value or act. value resp. operating source is parameterized.
If you have got the bus, replace the bus-PCB and/or the PCB –A1 Control
electronics and contact our service station.
If you have got no bus at all, recheck the parameter setting at
"P-INTERFACES:Op.-source=BUS" or "Reset-source=BUS". Or in menus
"P-speed default, P-process control, P-T-control, P-current control" a pa-
rameter is set to BUS. relocate these parameters to another source.
3131 Fault Contr. AD missing Flt>contr. AD - This error occurs when under "P-INTERFACE/P-Fieldbus/Contr. AD" the
parameterized bit in the control word is not specified by your control, the
reaction under "P-INTERFACE/P-Fieldbus/Rct. BUS = Fault" is parameter-
ized and a setpoint, the actual value or the operating source are parame-
terized to BUS.
If you have a BUS interface in the device, set the corresponding control
word bit of your control to 1. If you do not have a BUS interface in your
control, then check the parameterization of "P-INTERFACE/Op.-
source=BUS" or "Reset source=BUS" or the setpoint sources in the menus
of the control modes (e.g. "P-speed default, P-process control, …"). BUS
may not be actively selected here.
3132 Fault MainCntctr Flt>Main contctr. high With main contactor at the motor side only: The main contactor feedback
does not fit the read-out main contactor command. Recheck the wiring of
the circuit of the main contactor. Recheck the wiring of the main contactor
feedback contact (make contact). It has to go to the terminal that is param-
eterized at "P-OPERATION/Feedb.MC".