List of messages
Display messages
30 05/2020, 4BS0576F-004
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
3183 Fault P-failure 4/T= as no. 3180 as no. 3180 mean P-failure 4: as no. 3180
3184 Fault P-failure 5/T= as no. 3180 as no. 3180 mean P-failure 5: as no. 3180
3185 Fault P-failure 6/T= as no. 3180 as no. 3180 mean P-failure 6: as no. 3180
3186 Fault P-failure 7/T= as no. 3180 as no. 3180 mean P-failure 7: as no. 3180
3187 Fault P-failure 8/T= as no. 3180 as no. 3180 mean P-failure 8: as no. 3180
3188 Fault P-failure 9/T= as no. 3180 as no. 3180 mean P-failure 9: as no. 3180
3189 Fault P-failure 10/T= as no. 3180 as no. 3180 mean P-failure 10: as no. 3180
3190 Fault P-failure 11/T= as no. 3180 as no. 3180 mean P-failure 11: as no. 3180
3191 Fault P-failure 12/T= as no. 3180 as no. 3180 mean P-failure 12: as no. 3180
3192 Fault Interruption RS485 Flt>InterrpRS485 - The fault occurs if:
- the external display is not correctly connected to the RS485 interface or if
it is disconnected
- at P-INTERFACES/ P-RS485/RktRS485=failure is set and
- a RS485 setpoint source is parameterized.
If there is an external display at the RS485-interface –X51, connect / com-
mission as per description 4BS0751, chapter Communication / External
display.
If there is no external display, recheck the parameter setting in menus
"P-speed default, P-process control, P-T-control, P-current con-
trol:..Setpoint source". If a parameter is on "RS485" or, under
"P-OPERATION", if a parameter is on "…..ext.Bdf" relocate these parame-
ters to another source.
3194 Fault Thermistor X3:90/91 Flt>PTC X3:90/91 - The device, normally the motor whose thermistor is connected to terminals
–X3:90/91, is getting too hot. Recheck the motor. Recheck the machine,
usually the motor is overloaded.
3195 Fault Safe torque off trig Flt>STO tr. - This message is only output if parameter "P-INVERTER DATA/STO =
X2:20/24" is set for a two-circuit trip. One contact of the external safe
torque off must act on –X2:20, the second on –X2: 24. For this fault, one
circuit has a fault condition. Carefully check both safe torque off circuits.
NOTICE: Safety function; in case of doubt, contact our service station.
3200 !! Inverter fault !! download texts IF>download texts - as no. 3000, but not retained
3201 !! Inverter fault !! Power section U+! IF>Power.Sect.U+ as no. 3001, but not retained
3202 !! Inverter fault !! Power section U-! IF>Power.Sect.U- as no. 3002, but not retained
3203 !! Inverter fault !! Power section V+! IF>Power.Sect.V+ as no. 3003, but not retained
3204 !! Inverter fault !! Power section V-! IF>Power.Sect.V- as no. 3004, but not retained
3205 !! Inverter fault !! Power section W+! IF>Power.Sect.W+ as no. 3005, but not retained