32 05/2020, 4BS0576F-004
Msg-
Number
Display line 1
Display line 2
Text for event memory entry
Fault sup-
pression on
Description
3236 !! Inverter fault !! EarthCurrentMetering IF>I-EarthMeter. as no. 3036, but not retained
3237 !! Inverter fault !! Ter. X81:13 inactiv IF>X83:13 inactiv as no. 3037, but not retained
3238 !! Inverter fault !! Ter. X81:14 inactiv IF>X83:14 inactiv as no. 3038, but not retained
3239 !! Inverter fault !! Test safe torque off IF>Test STO as no. 3039, but not retained
3240 !! Inverter fault !! Test PTC X3:90/91 IF>Test X3:90/91 as no. 3040, but not retained
3244 !! Inverter fault !! PerformParameters IF>PerformParam as no. 3044, but not retained
3260 !! Fault !! Interr. RS485 (X26) Flt>RS485 (X26) as no. 3060, but not retained
3261 !! Fault !! Diff. current motor Flt>I-diff. Motor as no. 3061, but not retained
3275 !! Fault !! T-cabinet too low Flt>T-cab.t.low as no. 3075, but not retained
3277 !! Fault !! T-cooler 2 too high Flt>T-Cool.2 t.hi as no. 3077, but not retained
3278 !! Fault !! T-cooler 3 too high Flt>T-Cool.3 t.hi as no. 3078, but not retained
3279 !! Fault !! T-cooler 4 too high Flt>T-Cool.4 t.hi as no. 3079, but not retained
3280 !! Fault !! T-cooler 5 too high Flt>T-Cool.5 t.hi as no. 3080, but not retained
3281 !! Fault !! T-cooler 1 too low Flt>T-Cool.1 t.lo as no. 3081, but not retained
3282 !! Fault !! T-cooler 2 too low Flt>T-Cool.2 t.lo as no. 3082, but not retained
3283 !! Fault !! T-cooler 3 too low Flt>T-Cool.3 t.lo as no. 3083, but not retained
3284 !! Fault !! T-cooler 4 too low Flt>T-Cool.4 t.lo as no. 3084, but not retained
3285 !! Fault !! T-cooler 5 too low Flt>T-Cool.5 t.lo as no. 3085, but not retained
3294 !! Fault !! T-rectifier too low Flt>T-rect.t.low as no. 3094, but not retained
3295 !! Fault !! T-rectifier too high Flt>T-rect.t.high as no. 3095, but not retained
3296 !! Fault !! T-cabinet too high Flt>T-cab.t.low as no. 3096, but not retained
3300 !! Fault !! Overvoltage Flt>Overvoltage as no. 3100, but not retained
3301 !! Fault !! Undervoltage Flt>Undervoltage as no. 3101, but not retained
3303 !! Fault !! Earth fault Flt>Earth fault as no. 3103, but not retained
3304 !! Fault !! S7 inactive Flt>S7 inactive as no. 3104, but not retained
3305 !! Fault !! SC phase U Flt>Short Ph.U as no. 3105, but not retained
3306 !! Fault !! SC phase V Flt>Short Ph.V as no. 3106, but not retained
3307 !! Fault !! SC phase W Flt>Short Ph.W as no. 3107, but not retained
3308 !! Fault !! Fault tacho Flt>Fault Tacho as no. 3108, but not retained
3313 !! Fault !! T-CPU too high Flt>T-CPU too hi as no. 3113, but not retained