Electrical connection
6.6 Motor connection
Installation and Operating Instructions SINAMICS G180
98 Operating Instructions, 02/2019, 4BS0751-007
Jumpers for rated voltage preselection
Terminals -X101 and -X102 for an external control voltage
Terminal for preselection of the control voltage setting
View as in the picture: Internal power supply
Cable connected at connector -X200 : Power supply via terminals -X101 and -X102
Figure 6-1 Jumpers and terminals on the inverter
If a transformer is installed in a cabinet unit, the transformer connections must be changed to
the correct line voltage.
6.6
Motor connection
6.6.1
Motor selection
Three-phase asynchronous motors or three-phase synchronous motors can be used for your
inverter. The use of several motors simultaneously is permitted.
The total of the motor outputs must not exceed the inverter output. You may operate
smaller and larger motors in parallel on one inverter.
Take into account during the motor dimensioning that additional losses in the motor are
produced by the non-sine shaped motor current.
Note that a motor without external ventilation will be cooled less at speeds less than the
rated speed. Therefore, consult the motor manufacturer for the dimensioning of the
motor.
When using Siemens motors, refer to the list "UN03/UN04 Drehstrommotoren für
drehzahlverstellbare Antriebe" to find the relevant inverter output.