Electrical connection
6.6 Motor connection
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
101
Table 6- 6 Typical maximum motor cable lengths for different converter versions
Device type standard version
2T..-.....-.....D...
Version with strengthened du/dt
filter
2T..-.....-.....V...
Cable type
Cable type
NYCWY
NYY
NYCWY
NYY
Compact devices 400 V
2T..-(0…3)5400-...
connected to line supplies up
to 400 V
200 m 300 m 350 m 450 m
Compact devices 400 V
2T..-(0…3)5400-...
connected to line supplies >
400 V
150 m 200 m 300 m 350 m
Cabinet units 400 V
2T..-(7…8)(5…6)40.-...
connected to line supplies up
to 400 V
- - 300 m 350 m
Cabinet units 400 V
2R..-874..-...
150 m 200 m 300 m 350 m
Compact devices 500 V
2T..-(0…3)5500-...
- - 300 m 350 m
Cabinet units 500 V
2T..-(7…8)(5…6)50.-...
- - 250 m 300 m
Compact devices 690 V
2T..-(0…3)5600-...
150 m 200 m 300 m 300 m
Cabinet units 690 V
2T..-(7…8)(5…6)60.-...
100 m 140 m 250 m 300 m
Cabinet units 690 V
2R..-876..-...
150 m 200 m 300 m 350 m
The data in the table specifies the typical cable length in the sense of the distance between
the motor and the converter when parameterizing the standard clock cycle frequency. Larger
distances are also possible for individual types. Contact the factory for precise values if you
are in the limit range or if there is a long distance between the motor and converter.
NOTICE
Damage to the converter output filter
If you lay too many wires in parallel for the motor cable, the capacitive current in the motor
cable can increase unacceptably and destroy the converter output filter. In the case of
operation with several motors or parallel wiring of motor cables, the maximum possible
distance between converter and motor is reduced. Cabinet units are suitable for wiring in
parallel. Contact the factory for the precise values. Reduce the number of parallel wires to
permissible values.