EasyManua.ls Logo

Siemens SINAMICS G180 - Page 112

Siemens SINAMICS G180
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection
6.7 External control voltage
Installation and Operating Instructions SINAMICS G180
110 Operating Instructions, 02/2019, 4BS0751-007
Providing compact devices with the frame size K6 with 690 V
This instruction applies to compact units with frame size K6 with L × W 1125×500 mm and
690 V rated voltage.
Procedure
1. Turn the four fixing screws of the gray cover through 90° and lift up the cover.
2. Unscrew the blue cover at the screw above -X25 and lift up the cover.
3. Turn the four fixing screws of the swivel section by 90°, swivel the swivel section to the
right and clip the swivel section to the side panel.
4. The "fan power supply" board with five fine-wire fuses and the "switching power supply"
board are underneath.
5. On the "fan supply" board, change over the connector from socket -X100 for "internal" to
-X200 for "external".
6. Reassemble in the inverse order.
Note
Occurrence of malfunctions
Malfunctions can occur if you change over the connection of sockets
-X2 / 5 for "external" /
"internal" on the "switched
-mode power supply" board. Leave this connection on "external".