Electrical connection
6.7 External control voltage
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
113
Figure 6-5 Connection for external control voltage
Use the following connection values:
Maximum cross section
2.5 mm²
Protection
Miniature fuse in accordance with EN 60127: 6 A, slow acting,
maximum 100 VA
Miniature circuit-breaker: 6 A, characteristic D,
maximum 100 VA
Voltage +24 V DC ±15 %

Table of Contents