Commissioning
7.2 Checks with mains power supply and without motor
Installation and Operating Instructions SINAMICS G180
118 Operating Instructions, 02/2019, 4BS0751-007
Selecting application and mode
● It is not necessary to select an application for converters which have been fitted with a
signal controller at the factory.
● The parameter assignment is adapted in the factory when the unit is being tested and is
stored under the menu "P-DRIVE DATA/A" in the "Factory_Settings" application.
● Select the desired application under "P-DRIVE DATA/A", and select the desired operation
under "P-OPERATION/Opr.".
– Use the associated wiring diagram in the Appendix for this. The "Standard" application
is set as the default at the factory.
– For additional information, refer to the section titled "Standard" application"
(Page 168).
● If you would like to make other changes to the parameters, these changes can be made
at this point.
In this case, the parameter "P-DRIVE DATA/A=Standard" changes to "P-DRIVE
DATA/A=specific".
Note
Loss of all configured values
If you select other applications before the changed parameters have been saved, all
values already se
t will be lost. Save the changed parameters before selecting other
Checking mains power supply parameters
1. Set your mains rated voltage in the menu item "P-INVERTER DATA/V mains nom.".
If necessary, set the controller / fan transformer correctly.
2. For additional information, refer to the section titled "Mains connection" (Page 93).
1. Under "P-MOTOR DATA"/ first set the controller variant of the converter or the motor
type.