Operation
8.2 Standard mode settings
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
137
8.2.3
Mode "std dids"
(D)
Dynamic: Pushbutton mode
(S)
Static: Switch mode
Figure 8-5 Assignment of the control cable terminals for "std dids" mode
Control behavior for "Local" (dynamic)
Enter the command "Speed On" and "Speed Off" using the <On> and <Off> buttons on
the display.
Make the setpoint value setting using the <down arrow> and <up arrow> buttons.
Reset errors by pressing the buttons <S+I> simultaneously.
Control behavior for "Remote" (static)
Control the operation of "Speed on" with a switch at -X2:10. Enter the setpoint via control
cable terminal block -X2 with analog setpoint value 1.
When required use the reversing input -X2:16.
"Local" and "Remote" mode
"Emergency stop (NC)": If you open the contact at -X2:15, the drive decelerates down to
0 speed along the braking ramp for an emergency stop. The inverter clears all self-
holding functions.
"Reset" (NO): Reset errors and "Emergency stop" using a 24 V pulse at -X2:14.
"Controller release dynamic". Enable the inverter using a normally open contact at -X2:9.
The drive coasts to a stop if you open the contact at -X2:8. The inverter clears all self-
holding functions.