Operation
8.4 Controlling the external connections of the inverter
Installation and Operating Instructions SINAMICS G180
150 Operating Instructions, 02/2019, 4BS0751-007
-X26 for an external operator panel
Control cable terminal block -X2
Figure 8-17 DIL switch "S2"
The first four switches, S2: 1 / 2 / 3 / 4, define the voltage range for analog input 2, control
cable terminal -X2:54:
Table 8- 4 DIL switch "S2" - can be used to set the voltage range
Switch S2: 5 / 6 / 7 configures the analog input AI 2 as a current/voltage input, PTC
thermistor input, KTY84-130 input or PT100 input.
Table 8- 5 DIL switch "S2" - possible settings for AI 2