Operation
8.4 Controlling the external connections of the inverter
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
155
If you would like to use the software "IMS" to change the inverter parameters, the parameter
"P-INTERFACE/Para-Source" must be set to "Global" or "RS232". "Global" is the default
setting.
Using the "IMS" software, configure which COM port the cable on the PC will be
connected to.
The default setting is COM1.
Select the configuration under "Options/Drivers/RS232-485-Driver".
8.4.9
Connection for optional external display with RS 485
You have the option of connecting an external display at -X51 or at -X26. The connection
assignment for an external display with RS 485 is shown in the following diagrams.
Figure 8-23 External display connected at -X51
In order to be able to issue commands via an external display connected at -X51 to the
inverter, set the corresponding command source in the parameter assignment to "RS 485".
Figure 8-24 External display connected at -X26
The -X26 interface is only suitable for an external display, for instance installed in the cabinet
door.
In order to be able to issue commands via an external display connected at -X26 to the
inverter, set the corresponding command source in the parameter assignment to "intern".