Technical data
C.1 Technical data for transportation
Installation and Operating Instructions SINAMICS G180
194 Operating Instructions, 02/2019, 4BS0751-007
C.1
Technical data for transportation
Carefully observe the following environmental conditions for transport according to
EN 60721-3-2:
Environmental conditions for inverter transport
Climatic conditions
Class 2K3 acc. to EN 60721-3-2
Atmospheric pressure
700 mbar1060 mbar, corresponds to max. 3000 m above sea level
Ambient temperature
- 25 °C … + 70 °C
Humidity rating Maximum relative humidity if the temperature of the inverter slowly increases by
40 K: 95 %
Maximum relative humidity if the device is brought immediately from - 25 °C to
+ 30 °C: 95 %
Maximum absolute humidity if the device is brought immediately from + 70 °C to
+ 15 °C: 60 g/m
3
Mechanical conditions
Class 2M2 according to EN 60721-3-2
Vibration load
- Deflection
- Acceleration
3.1 mm at 5 ... 9 Hz
10 m/s² at 9 ... 200 Hz
Shock load
- Acceleration
100 m/s² at 11 ms
Chemical conditions
Class 2C2 according to EN 60721-3-2
Biological conditions
Class 2B1 according to EN 60721-3-2
C.2
Technical data for storage
Carefully observe the following environmental conditions for storage according to
EN 60721-3-1:
Environmental conditions for inverter storage
Climatic conditions
Class 1K4 acc. to EN 60721-3-1 for the temperature
Class 1K3 acc. to EN 60721-3-1 for the relative humidity
Atmospheric pressure
860 mbar1060 mbar, corresponds to max. 1000 m above sea level
Ambient temperature
- 25 °C … + 70 °C
Humidity rating
5 % … 95 %, 1 g/m³29 g/
Mechanical conditions
Class 1M2 according to EN 60721-3-1
Vibration load
- Deflection
- Acceleration
1.5 mm at 5 ... 9 Hz
5 m/s² at 9 ... 200 Hz
Shock load
- Acceleration
40 m/s² at 22 ms
Environmental class/
Chemical conditions
Class 1C2 according to EN 60721-3-1
Organic/biological conditions
Class 1B1 according to EN 60721-3-1