EasyManua.ls Logo

Siemens SINAMICS G180 - C.9 Technical Data of the Direct Water Cooling

Siemens SINAMICS G180
218 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical data
C.7 Technical data of the control cable terminals
Installation and Operating Instructions SINAMICS G180
202 Operating Instructions, 02/2019, 4BS0751-007
Technical data of the control cable terminals
Conductor cross-section –X2
rigid / flexible: 0.5 m2.5 mm²
Relay outputs -X2:3042 5 V … 250 V AC / 1 A, 15 AC
5 V … 30 V DC / 1 A
> 30 V … 60 V DC / 120 mA
> 60 V … 250 V DC / 60 mA
With peripheral board 3 or 4 only:
Relay outputs -X2:4349
Minimum switching load: 12 V / 100 mA
Digital inputs -X2:8 ... 16 Low: -3 V … +5 V
High: 13 V32 V
Floating
Typically 12 mA for High
Digital input safe torque off (only
with peripheral board 3 or 4):
-X2:20
Low: -3 V … +5 V
High: 13 V … 32 V
Floating
Typically 12 mA for High
Response time: ≤ 5 ms
Analog inputs -X2:5053 Voltage input 0 V … ± 10 V, 200
Terminal 52 and 54 or current input
0 mA or 4 mA
*)
… ± 20 mA, 100 Ω,
Terminals 50 and 53
Supply voltages on potential of the
analog inputs for diverse sensors:
Terminal 55: 24 V DC, max. 300 mA
Terminal 56: 15 V DC, max. 150 mA
Terminal 57: 10 V DC, max. 10 mA
Terminal 58: -10 V DC, max. 10 mA
Digital inputs X2:27, 28 Low: -3 V … +5 V
High: 13 V32 V
Floating on potential of the analog inputs
Typically 2.4 mA for High
Direct connection of PTC thermistors
Reference potential for PTC thermistor:
Terminal -X2:58 (-10 V).
The voltage over the PTC thermistor is approx. 2.5 V
Can also be used as f or n input.
Digital input -X2:29 Low: -3 V … +5 V, high: 13 V32 V
Floating on potential of the analog inputs, typically 2.4 mA for High
Can also be used as f or n input
Analog outputs -X2:6063 With automatic changeover current or voltage, floating:
Load < 300 Ω: 0 mA or 4 mA
*)
20 mA
Load > 1 kΩ: 0 V10 V
Supply voltages on potential of the
analog outputs:
Terminal 70: 24 V DC, max. 300 mA
*)
0 mA or 4 mA can be parameterized.

Table of Contents

Other manuals for Siemens SINAMICS G180

Related product manuals