Technical data
C.9 Technical data of the direct water cooling
Installation and Operating Instructions SINAMICS G180
204 Operating Instructions, 02/2019, 4BS0751-007
Technical data of the direct water cooling
Technical data
2T3A-77401-200 … 2T3A-77401-315
2T3A-77501-250 … 2T3A-77501-400
2T3A-77601-250 … 2T3A-77601-400
BG S2
2T3A-77401-400
2T3A-77501-500
BG S21
2T3A-77401-500 … 2T3A-77401-630
2T3A-77501-560 … 2T3A-77501-800
2T3A-77601-560 … 2T3A-77601-910
BG S3
If you connect several converters in parallel, the technical data are multiplied according to
the number of systems. The water flowrate for type 2T 6 A-7 5 69 4-925 with four converter
systems is e.g. 4×2000 l/h.
The water-cooled units BG S1 to BG S21 have the same cabinet width as the air-cooled
units.
In the case of units with frame size S3, the cabinet width when compared to the air-cooled
version increases as follows:
Cabinet increase for water cooling
Units with two or three systems
Water cooling - Ambient conditions
Degree of protection IP55
IP54 with operator panel in the door
Water quality For industrial water, see section "Permissible substance values for the cooling
Permissible coolant temperature
+10 °C … +25 / 30°C (depends on the power, see converter documentation)
Permissible ambient temperature
In operation: +1 °C … +55 °C
Water cooling - Water pressure and amount of water
Water flow rate [l/h] 720 1200 2000
Min. operating pressure [bar] 1 1 2,5
Max. operating pressure [bar] 6 6 6
Pressure loss [approx. bar] 0,5 0,7 1,4