Technical data
C.11 Threshold values for fan control system
Installation and Operating Instructions SINAMICS G180
206 Operating Instructions, 02/2019, 4BS0751-007
Threshold values for fan control system
The fan control system detects the three following states: OFF, SLOW and FAST.
● OFF: The fans are OFF if the unit is not switching and all relevant temperatures are below
the thresholds for FAST.
● SLOW: The fans operate slowly if the unit is turned on (= is switching) and all relevant
temperatures are below the thresholds for FAST.
● FAST: The fans operate fast if one of the relevant temperatures is higher than the
threshold for FAST irrespective of whether or not the unit is turned on.
Table C- 5 Threshold values for fan control system
Parameter P-INVERTER DATA.fan
1)
1)
1)
Air/water cooled
() Where relevant, values in brackets should be seen as switching hysteresis.
The devices and the associated system components are rated for an ambient temperature of
40 °C and installation altitudes of up to 1000 m above sea level.
The following tables specify the permissible output currents as a function of the installation
altitude and ambient temperature.
Note also the information in section "Voltage derating" (Page 209).