Description
3.3 Accessories
Installation and Operating Instructions SINAMICS G180
Operating Instructions, 02/2019, 4BS0751-007
59
Note
Suitable fiber types
HCS as well as APF cables (POF) are suitable for connecting to the fiber optic sockets.
Typical cable lengths are up to 100
m (HCS) or up to 50 m (POF).
Table 3- 5 PROFINET board - external elements
NS
"Network status"
display
Off Offline No power supply or no connection with
Green, lit Online (status:
RUN)
Connection established with the IO
controller, IO controller in the RUN
Flashing green
(1 Hz)
Online (status:
STOP)
Connection established with the IO
controller, IO controller in the STOP
Green flashing (3x
Flashing Flashes three times in order to identify
the slave in the network.
Red, lit Fatal event Fatal, internal error.
This display occurs in conjunction with
a red "Module status" LED.
Flashing red
(1 Hz)
Error, station
name
A station name has not been assigned
(factory setting).
Flashing red
Error, IP address An IP address has not been assigned
Flashing red
(3 Hz)
Error, configura-
tion
The reference configuration (expected
identification) differs from the actual
configuration (real identification) of the
MS
"Module status"
display
Off Not initialized No power supply voltage or module in
the SETUP or NW_INIT state
Green, lit Normal operating
The module has exited the NW_INIT
Flashing green
Diagnostic
At least one diagnostics event is active.
Red, lit
Device in the EXCEPTION state
Fatal event Fatal internal event.
This display occurs in conjunction with
a red "Network status" LED.
Flashes red/green
alternating
Firmware update Do not switch off the module.
Switching off the module during the
update can result in permanent dam-