B.6 18-Cell System Speci󹪝cations
Table B-7 21/24-Cell System Speci󹪝cations
Cells in Drive
(without Redundancy)
Output Voltage
Available L-L (with O-M)
Hp Range Power Cell Types
(Continuous Current Rating)
18 8000 V (8400 V) 4000 - 13000 550, 600, 780 A
Parameters Ratings
Input Line Voltage 3.0, 3.3, 4.16, 4.8, 6.0, 6.3, 6.6, 6.9, 7.2, 8.4, 10, 11, 12, 12.47, 13.2, or 13.8 kV
3 - phase; +10 % / -5 %
Input Frequency 50 or 60 Hz ±5 %
Input Power Factor > 0.95 above 10 % load
Input Harmonics ≤ 5 % TDD with ambient THDv ≤ 2 %
Minimum E󹪟ciency 2Q
4
≥ 96 % VFD → 96 % Al; 96.5 % Cu
Output Voltage 18-Cell
8010 V / 8410 V
Output HVF <0.03
Output dv/dt < 3000 V / µS
Overload Capacity
1
110 % 1 minute / 10 minute
Output Frequency & Drift
2
0.5 - 330 Hz, ±0.5 % (derates at <10 Hz and at >167 Hz)
Output Torque 10 - 167 Hz rated torque
Design Life 20 years
Auxiliary Voltage
3
380 V, 400 V, 415 V, 50 Hz
460 V, 480 V, 60 Hz; 3 - phase
Enclosure Type NEMA 1 Ventilated
Degree of Protection IP42
Ambient Temperature 0 - 40 °C (maximum 50 °C, derating starts from 40 °C on)
Altitude 0 - 3300 ft. (1000 m) without derating maximum
Sound Level 82 dB(A)
Cooling Ventilated, forced air-cooled with integrated fans
1. 780A Power Cells do not have 110% overload capability
2. For high speed projects (>167 Hz), consult Siemens
3. Consult factory for availability of auxiliary voltages other than shown
4. Input Transformer Winding Conductor Material (CU or AL)
Technical Data
B.6 18-Cell System Speci󹪝cations
Type 6SR5 Air-Cooled
112 Operating Instructions, AK, A5E39390112