Fiber Optic
Removed
Figure 10-16 Fiber Optic Removed
Note
Refer to the 󹪝ber optic removal photos shown immediately preceding this Note.
Be sure to wear proper Personal Protective Equipment (PPE).
Use the Siemens cell lifter to remove cell from System.
Disconnect all system bus and cables from the front of the cell. This includes T1,T2 L1, L2, and
L3 connections. When bypass option is applicable, the T1 and T2 output bolted connections
are made on the bypass contactor.
Maintenance
10.7 Remove and Replace
Type 6SR5 Air-Cooled
Operating Instructions, AK, A5E39390112 83