Technical data
6.5 400 V converters
Power Module PM240-2
92 Hardware Installation Manual, 01/2020, A5E33294624B AL
Table 6- 20 PM240-2, IP20, frame size C, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3210-1PE22-7UL0
6SL3210-1PE22-7AL0
6SL3210-1PE23-3UL0
6SL3210-1PE23-3AL0
LO base load power 11.0 kW 15.0 kW
LO base load input current 32.6 A 39.9 A
LO base load output current 26.0 A 32.0 A
HO base load input current
HO base load output current 18.0 A 26.0 A
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
3NA3820 (50 A)
Required cooling air flow
Table 6- 21 PM240-2, PT, frame size C, 380 V … 480 V 3 AC
Article No. without filter
Article No. with filter
6SL3211-1PE23-3UL0
6SL3211-1PE23-3AL0
LO base load input current
LO base load output current
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
3NA3820 (50 A)
1)
Required cooling air flow
Weight without filter 5.8 kg
Weight with filter 6.3 kg
approx. 0.3 kW through the heatsink