Description: Diagnostics parameter to display additional information for internal software errors.
Only for internal Siemens troubleshooting.
Description: Sets the sampling time for the Terminal Module 54F (TM54F).
Description: Sets the delay time for the test of the digital outputs 0 ... 3 (DO 0 ... 3).
Within this time, for a forced checking procedure of the digital outputs, the signal must have been detected via the
corresponding digital input DI 20 ... 23.
Dependency: Refer to: p10003, p10007, p10041, p10046
Description: Sets the monitoring time for the discrepancy for the digital inputs.
The signal states at the two associated digital inputs (F-DI) must assume the same state within this monitoring time.
Note: F-DI: Failsafe Digital Input
r9999[0...99] Software error internal supplementary diagnostics / SW_err int diag
CU_CX32, CU_S Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dynamic index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
- - -
p10000 SI sampling time / SI t_sample
TM54F_MA,
TM54F_SL
Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1.00 [ms] 25.00 [ms] 12.00 [ms]
p10001 SI delay time for test stop at DO 0 ... 3 / SI t_delay DO
TM54F_MA,
TM54F_SL
Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
2.00 [ms] 2000.00 [ms] 500.00 [ms]
p10002 SI discrepancy monitoring time / SI discrep t_monit
TM54F_MA,
TM54F_SL
Can be changed: C2 Calculated: - Access level: 3
Data type: Floating Point Dynamic index: - Func. diagram: 2850, 2851
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Expert list: 1
Min Max Factory setting
1.00 [ms] 2000.00 [ms] 12.00 [ms]