Function Diagrams
Setpoint channel
2-1228
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
Figure 2-115 3030 – Main/supplementary setpoint, setpoint scaling, jogging
- 3030 -
Function diagram
87654321
DO: SERVO, VECTOR, VECTORGL, VECTORMV
SINAMICS
19.03.07 V02.05.00
Setpoint channel - Main/supplementary setpoint, setpoint scaling, jogging
r1077
r1073
r1078
+
+
Jog 1
r0898.8
Jog 2
r0898.9
fp_3030_51_eng.vsd
[2501.7]
p1055
[2501.7]
p1056
Suppl setp scal
(1)
p1076[C]
Main setp scal
(1)
p1071[C]
Main setpoint
(1024[0])
p1070[C]
Supplement setpoint
(0)
p1075[C]
p2901
Fixed value 2 [%]
p2900
Fixed value 1 [%]
AOP30
JOG
LOCAL
REMOTE
I
O
[2501.2]
0
1
PcCtrl active
r0807.0
[3040.1]
[2501.1]
<2>
<2>
<3>
0 0
0 1
1 0
1 1
n_set_1
Jog setpoint 1
-210 000.000...210 000.000 RPM
p1058[D] (100.000)
Jog setpoint 2
-210 000.000...210 000.000 RPM
p1059[D] (100.000)
[3040.1]
Keep old setpoint
<100>
<101>
Refer to [1020.7]
p0115[3]
1
0
&
Synchronization
No OFF1
No OFF2
No OFF3
–
+
f _slip
[6730.2]
r3804
Sync f_targ
[7020.8]
<1> AOP30 for SINAMICS GM150 only.
<2> Only active in LOCAL mode (r0807.0 = 1) [2501.2].
<3> Jogging can only be activated in the following operating states (sequencer see [2610]):
- For SERVO and VECTOR: In the “Ready to start (S2)“ operating state.
- For VECTORGL and VECTORMV: In the “Operation (S4)“ operating strate.
<100> For SERVO, the following applies: Only if the function module “extended setpoint channel“ is activated (r0108.8 = 1).
<101> To view the pre-assignment of the sampling times in p0115, refer to p0112.
<1>