Siemens SINAMICS S Series - F07432 Drive: Synchronous motor without overvoltage protection; F07433 Drive: Closed-loop control with encoder is not possible as the encoder has not been unparked; F07434 Drive: It is not possible to change the direction using p1821 with the pulses enabled; F07435 (N) Drive: Setting the ramp-function generator for sensorless vector control

Siemens SINAMICS S Series
1816 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Faults and Alarms
List of faults and alarms
3-1542
© Siemens AG 2007 All Rights Reserved
SINAMICS S List Manual (LH1), 07/2007
F07432 Drive: Synchronous motor without overvoltage protection
Drive object: SERVO
Reaction: OFF2 (OFF1)
Acknowledge: IMMEDIATELY
Cause: Under voltage conditions, a synchronous motor can generate an overvoltage condition that can destroy the drive sys-
tem.
Fault value (r0949, interpret hexadecimal):
Associated Drive Data Set (DDS).
Remedy: Overvoltage protection can be implemented in the following ways:
- limit the maximum speed (p1082) without any additional protection.
The maximum speed without protection is calculated as follows:
Rotary motors: p1082 [rpm] <= 11.695 * p0297/p0316 [Nm/A]
Linear motors: p1082 [m/min] <= 73.484 * p0297/p0316 [N/A]
- use a voltage protection module (VPM) in conjunction with the function "Safe Torque Off" (p9601, p9801).
When a fault condition exists, the VPM short-circuits the motors. During the short-circuit, the pulses must be can-
celed - this means that the terminals for the function "Safe Torque Off" must be connected to the VPM.
When using a VPM, p0643 must be set to 1.
- activating the internal voltage protection (IVP) with p1231 = 3.
See also: p0643 (Overvoltage protection for synchronous motors), p1231 (Armature short-circuit / DC brake config-
uration)
F07433 Drive: Closed-loop control with encoder is not possible as the encoder has not been
unparked
Drive object: SERVO
Reaction: NONE (OFF1, OFF2, OFF3)
Acknowledge: IMMEDIATELY
Cause: The changeover to closed-loop control with encoder is not possible as the encoder has not been unparked.
Remedy: - check whether the encoder firmware supports the "parking" function (r0481.6 = 1).
- upgrade the firmware.
Note:
For long-stator motors (p3870.0 = 1), the following applies:
The encoder must have completed the unparking procedure (r3875.0 = 1) before a changeover can be made to
closed-loop control with encoder. The encoder is unparked with a 0/1 edge at BI: p3876 and remains unparked until
a 0 signal is again present.
F07434 Drive: It is not possible to change the direction using p1821 with the pulses enabled
Drive object: SERVO, VECTOR
Reaction: OFF2
Acknowledge: IMMEDIATELY
Cause: A drive data set was selected - with the pulses enabled - that has a different parameterized direction (p1821). It is
only possible to change the motor direction using p1821 when the pulses are inhibited.
Remedy: - change over the drive data set with the pulses inhibited.
- ensure that the changeover to a drive data set does not result in the motor direction of rotation being reversed (i.e.
for these drive data sets, the same value must be in p1821).
See also: p1821 (Direction reversal rotating field)
F07435 (N) Drive: Setting the ramp-function generator for sensorless vector control
Drive object: SERVO, VECTOR
Reaction: OFF2 (IASC / DCBRAKE, NONE, OFF1, OFF3)
Acknowledge: IMMEDIATELY
Cause: During operation with sensorless vector control (r1407.1) the ramp-function generator was stopped (p1141) or
bypassed (p1122). An internal setting command of the ramp-function generator output caused the set setpoint speed
to be frozen or was not able to be realized.